Check here the checklist for installation: Checklist hardware on-site visit /or installation

Ethernet connected Hub - no longer available

During the installation process changes will be made to the firewall. Therefore, it is advised to contact your IT-department our network specialist.
Step 1. Place the hubs at the location that was provided to you by the project engineer. In the case that no location was provided or the location is not accessible find a nearby or central location equipped with an ethernet connection and wall wart. E.g. in the gap of a raised ceiling or in the IT room.
Caution! The hub must never be unplugged after installation. Choose a location where accidental unplugging will not occur.

...

Following table lists the IP addresses that outgoing traffic (sensor data) goes to here: List of IP addresses for outgoing traffic

Expand
titleIP Addresses needed for Outgoing traffic

We sync all our hubs to the same open NTP (network time protocol) servers so we have consistent timings in our data warehouse.

How to use below table

  • as mentioned above, ideally just the ports mentioned should be opened (outbound)

Note

We recommend not to use specific IP addresses or DNS destinations in the firewall as they can and probably will change in the future!

  • protocol information and AL descriptions are extra

Depending on the environment main location, Spacewell Workplace tenants are created in an EU- or US-environment. Hence, for some ports to be opened, the destination address might be a different one:

  • eu: spacewell.eu1.cloud.thethings.industries

  • usa: spacewell.nam1.cloud.thethings.industries

Destination

Port

Protocol

Direction

AL description

3.openwrt.pool.ntp.org

53;123

TCP

Outbound

DNS;NTP

2.openwrt.pool.ntp.org

53;123

TCP

Outbound

DNS;NTP

1.openwrt.pool.ntp.org

53;123

TCP

Outbound

DNS;NTP

0.openwrt.pool.ntp.org

53;123

TCP

Outbound

DNS;NTP

80

TCP

Outbound

HTTP

www.google.com

443

TCP

Outbound

TLS / SSL

54.242.161.211 clc1.trackio.ch

80

TCP

Outbound

HTTP

443

TCP

Outbound

TLS / SSL

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balancer REST API

eu: spacewell.eu1.cloud.thethings.industries

usa:

spacewell.nam1.cloud.thethings.industries

443

TCP

Outbound

TLS / SSL

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balancer REST API

backend.tabs.io

443

TCP

Outbound

TLS / SSL

mh.sm.tc

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balancer REST API

lns.eu.thethings.network 443

443

TCP

Outbound

TLS / SSL

rjs.sm.tc

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balancer REST API

cups2.trackio.ch

8888

TCP

Outbound

TLS / SSL

gwrel.trackio.ch

18777

TCP

Outbound

Hub Management

mtun.cobundu.com

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balancer REST API

18777

TCP

Outbound

Hub Management

Port

Protocol

Direction

AL Description

53

TCP

Outbound

DNS

123

TCP

Outbound

NTP

443

TCP

Outbound

TLS/SSL

80

TCP

Outbound

HTTP

7000

TCP

Outbound

WSS

7001

TCP

Outbound

Load Balancer

7002-7512

TCP

Outbound

Load Balanced REST API

8888

TCP

Outbound

TLS/SSL

18777

TCP

Outbound

Hub Management


Step 3. Connect the hub
Step 3.1 Connect the ethernet cable to the blue port
(Indicated by A)
Step 3.2 Connect the power cable
(Indicated by B)
Step 3.3 Plug in the power adapter
Preferably in a UPS and surge protector
Step 3.4 Check the status LEDs
After booting following LEDs should be solid green
Power | Lora | Ethernet
Caution! First time boot procedure takes 15 to 20 minutes
Longer times may be observed with bad connectivity

...

Step 4. Let your Cobundu PE check the connection of the hub on the cloud platform


Ethernet hub (via 4G) - no longer available

Step 1. Place the hubs and 4G routers at the location that was provided to you by the project engineer. In the case that no location was provided or the location is not accessible find a nearby or central location equipped with a wall wart and decent reception.
Caution! The hub and 4G router must never be unplugged after installation. Choose a location where accidental unplugging will not occur.

...

Step 4. Let your Cobundu PE check the connection of the hub on the cloud platform

...

Trouble shooting a hub

Image Removed
Image Added

Status Lights

Image Removed
Image Added


Solid Green
Feature is operating correctly.

Image Removed
Image Added


Solid Orange
Feature is not operating correctly.

Icons

Image Removed

Image Added


Ethernet LED
Indicates the state of the WAN and LAN ports

Image Removed
Image Added

LoRa LED
Indicates the state of the LoRa network

Image Removed
Image Added

Wi-Fi LED
Indicates the state of the Wi-Fi Network (Feature deactivated by default)

Image Removed
Image Added


Power LED
Indicates that the Base Station is
functioning normally


Ethernet LED The ethernet LED shows the connectivity status between the Hub and the Platform Off: No network → Check if the ethernet cable is plugged in on both ends. Blue port for the Hub. Orange: Connection not established → Check if the correct ports are opened. For Hubs connected to 4G check for sufficient throughput and instalment of 4G antennas Green: Connected
LoRa LED The LoRa LED shows the readiness of receiving messages from the sensors. The hub will not accept messages if it is not connected to the platform Off: Not ready → Check connection to platform Green: Ready
WI-FI LED The hubs are preconfigured not to send out any wifi signals. The light may turn on during initial boot but will turn itself off after configuration is loaded.
Power LED Off → Powered off Flashing Green → Boot mode Flashing Orange/Green → Reset mode Green → Powered on


When a tab hub (not mini) does not come online, you might be requested to manually update the hub firmware on site: check out the following page on (new) Manually Update Ethernet Hub* Firmware TTES (direct via LAN), describing the steps to take.

WiFi Configuration

If WiFi needs to be turned off (recommended), please follow these steps:

Configuring the Hub will let you set up the Hub as a router, WIFI client, WIFI extender, or WIFI off. It will also let you choose between DHCP and Static IP for ethernet based connections.
Step 1. Check the firmware version
Step 1.1 Join the hubs initial open Wi-Fi network (Tabs-xxxxxxx) or connect the hub with a LAN cable (plugged into a black port) to your computer
Step 1.2 Open the Tabs (Tracknet) configuration guide
Step 1.3 Select button "Hub Info"
Step 1.4 Check if the current firmware version is 1.25.02 or later

...


Step 2. Factory reset the hub with internet unplugged.
Caution! If the hub is connected to the internet it will reconfigure to the standard MCS configuration
Step 3. Join the hubs initial open Wi-Fi network (Tabs-xxxxxxx) or connect the hub with a LAN cable (plugged into a black port) to your computer
Step 4. refresh the Tabs (Tracknet) configuration guide page
Step 5. Select button "Hub Setup"
Step 6. Follow the configuration steps of the configuration tool.

...


Frequently asked questions – FAQ

Can I reset the hub?
Yes, Press the reset button located between the power and blue ethernet until the power LED start flashing orange/green (approx. 20 seconds)The hub will reset back to the original MCS configuration, this can take up to 20 minutes.
Can I run my own configuration?
No, the hubs are configured with the MCS configuration.Trying to reconfigure the hub with the tabs app will lead to malfunctioning hardware
How can I test network throughput?
Connect your laptop to the connection under testGo to a speed test website, e.g. https://www.speedtest.net/Run the test
Can I configure the firewall with a fixed endpoint or IP?
No, the hubs are configured to connect to load balancers. The end points of these load balancers can and will change over time.
Can the Hub be configured with a fixed IP address?
Yes, but this is not in the standard scope. The configuration of a fixed IP is only possible using ethernet and has to be performed by a project engineer on site. This brings additional costs and will alter the project timeline.
Can the Hub connect over WIFI?
Yes, but this is not in the standard scope. The configuration of a WIFI connectivity is only possible using DHCP and has to be performed by a project engineer on site. This brings additional costs and will alter the project timeline.
Can the sensors be installed before the Hub?
No, always wait for the confirmation of the project engineer.
Is the battery of a sensor replaceable?
Yes, a sensor uses a single LiSOCl2 (Lithium Thionyl Chloride) ½ AA battery.
To replace the battery, follow the battery replacement instructions in the separate guide or on the following link:
https://tabshelp.zendesk.com/hc/en-us/articles/360001179514-How-do-I-replace-the-batteries-in-Tabs-devices-
Can the sensors by used with the Tabs app?
No. The sensors are directly linked to the COBUNDU platform and can not be remapped to the Tabs smart home app.

...