Difficulty: expert
Content
Table of Contents | ||||
---|---|---|---|---|
|
Learning Objectives
After reading this article, you’ll be able to:
Prepare your environment to start using Milesight
Configure your Milesight CO2 devices
Milesight CO2 Sensor gathers data for Humidity + CO2 + Temperature.
Prerequisite: Gateway
Milesight sensors connect over the LoRa network. Make sure you install your LoRa hub before installing the sensors (check out LoRa Gateways, Hubs installation guides for more information).
Packing list
Sensor configuration
All sensor settings can be configured via a smartphone application with NFC (Near Field Communication)
Make sure to use a NFC supported mobile phone and follow below steps:
Remove the back panel of the sensor with a small screwdriver.
Info |
---|
Keep the back panel and the sensor together, since the sensor ID is indicated on the back panel! |
Install the batteries that come with the device.
Do not reverse the direction of batteries when installing.
Note |
---|
The device can only be powered by ER14505 Li-SOCl2 batteries (not alkaline batteries). Using batteries other than the ones provided may result in loss of performance and battery life, and also damage to the device. Dispose of properly, observing environmental protection rules. |
Press and hold the power button (on the back of the device) for more than 3 seconds to power up
Note |
---|
Don’t press longer than 10 seconds or the device will reset. |
Download and install “Milesight ToolBox” App from Google Play or Apple App Store.
Enable NFC on the smartphone and launch Milesight ToolBox app.
Info |
---|
Make sure the reading completes 100% to make sure you’re working on the correct device. |
Expand | ||
---|---|---|
| ||
Info |
---|
|
* Smartphone NFC area might be in a different location depending on phone brand and model. Check your phone specifications to make sure you’re tapping the correct area to the Milesight CO2 sensor.
Calibration
Go to Settings (header) > Calibration settings to calibrate the CO2 value.
Info |
---|
Take these actions in fresh air, because the calibration needs to happen outside. |
Make sure Auto Background Calibration value is turned on.
Select Manual Calibration
Confirm the pop-up asking to start calibration
The app will prompt you to scan the device again
Hold the smartphone with NFC area to the Milesight CO2 sensor to start manual calibration
Once successful, you will get a message
As soon as the app confirms manual calibration ready, place the device outdoors for minimum 20 minutes
Info |
---|
Make sure to select “Manual Calibration” (otherwise calibration might take more than a week) |
Apply configuration on other Milesight CO2 devices
Info |
---|
On the start screen of the app, it will indicate the device ID of the device you started with, but the app allows you to start calibration on other devices too! |
Info |
---|
Keep in mind that there will be a variance in the value per sensor to sensor of up to +/-30% (industrial standard) |
Next steps
Now that all devices are calibrated, they can be installed following the instructions on Milesight CO2 Sensor Installation.