Double sided tape (see Tabs Sensors installation guides for more information)
Hubs
Elsys connect over the LoRa network. Make sure you install your LoRa hub before installing the sensors (check out LoRa Gateways / Hubs installation guides for more information).
Sensor Installation
1. Decide HOW to install
• Check if locations apply to prerequisites
...
4. Attach the sensor part to the back panel.
Sensor configuration (optional)
All sensor settings can be configured via a smartphone application with NFC (Near Field Communication)
...
- Download ELSYS “Sensor Settings” application from Google Play and install it on a smartphone or tablet. The device must support NFC.
- Enable NFC on the device and start the application.
- Place your device on top of the NFC antenna on the sensor.
- Remove the device. Current settings will be displayed in the application.
- Use the application to change settings
- Change the Timebase from 300 to 900 Sec
- Change the Motion configuration from PIR:Count to Off
- Change the AppEUI under Sensor keys from 0 to 70b3d57ed002286a
- ONLY FOR USA: Change the Frequency plan under Version 2 features from "3 EU868" to "4 US915"
- Quickly tap the device on top of the NFC antenna to give the new settings to the sensor. Make sure that the application confirms your new settings.
- Wait for the sensor to reboot (5 sec), indicated by the LED flashing. Sensor settings have been updated.
Studio Mapping
On the back panel of the sensor, you will find the Device ID (format a81758fffe0xxxxx). This is the ID to use to do the mapping in Studio.