Prepared by
...
Simon de Jager
...
Last edited
...
...
Version
...
0
Table of content
Table of Contents |
---|
Elsys comfort sensors check for Humidity + CO2 + Temperature.
...
For sensor installation (comfort), we advise using double sided tape.
At Spacewell, we always use double sided tape from brand Tesa Powerbond Ultra Strong (5m * 19mm) for the motion sensors. This tape is strong and works for all the different types of sensors.
We estimate that you use 3-5cm per sensor. So, you can probably hang roughly 100 sensors per roll.
Best practice:
- Tape: Press the tape in the crook of the sensor to ensure good adhesion / bigger surface area
Inserting the batteries
If 1 sensor (or just a few) is purchased, the batteries are IN the sensor; they can be activated by pulling the tab.
Only from more/bigger quantities the sensors are packed separately in a plastic tray (2 batteries are needed per sensor). 1 tray = +/- 75 batteries
1. Remove the back panel of the sensor with a small screwdriver.
...
3. Mount the back panel on the wall using some of the six mounting holes. It may : there are 6 points where you can set a screw, mount using at least 2 screws. Alternatively, it can also be mounted using adhesive tape.
...
All sensor settings can be configured via a smartphone application with NFC (Near Field Communication)
NFC Configuration (optional) (Android phone with Elsys app needed!!)
- Download ELSYS “Sensor Settings” application from Google Play and install it on a smartphone or tablet. The device must support NFC.
- Enable NFC on the device and start the application.
- Place your device on top of the NFC antenna on the sensor.
- Remove the device. Current settings will be displayed in the application.
- Use the application to change settings
- Change the Timebase from 300 to 900 Sec
- Change the Motion configuration from PIR:Count to Off
- Change the AppEUI under Sensor keys from 0 to 70b3d57ed002286a
- ONLY FOR USA: Change the Frequency plan under Version 2 features from "3 EU868" to "4 US915"
- Quickly tap the device on top of the NFC antenna to give the new settings to the sensor. Make sure that the application confirms your new settings.
- Wait for the sensor to reboot (5 sec), indicated by the LED flashing. Sensor settings have been updated.
...