DifficultySchwierigkeitsgrad: expertExperte
Inhalt
Table of Contents | ||||
---|---|---|---|---|
|
Learning Objectives
After reading this article, you’ll be able to:
Gather all information needed to create a sensor plan for occupancy & headcount sensors
Identify obstructions for installing hardware
Create a sensor plan which indicates hardware installation location to all stakeholders
A Sensor Plan is a document that shows all stakeholders (Facility Managers, IT, Installation partner, …) where sensors and other hardware will be installed, taking into account sensor detection areas, obstructions etc.
In the course of a Workplace Analytics project, the Sensor Plan will provide concrete examples and bring forward discussion topics.
Means of Communication between all stakeholders
A Sensor plan can be used as means of communication between all stakeholders on
Types of sensors and hardware to be installed (facility managers or technicians on site might not have been part of procurement process, so depending on for example headcount kind of sensor, you need to provide cabling/a hole in the ceiling; displays need cabling etc)
Number of sensors and other hardware to be installed
Installation location of sensors and hardware (for example where the hole needs to be in the ceiling compared to the detection area)
Room numbers / names for each meeting room/bubble/work place/comfort area that will be covered by sensors
Info |
---|
Tip: Create a PowerPoint doc in format A3, so it can easily be printed in a large format for installers. |
Lernziele
Nach der Lektüre dieses Artikels werden Sie in der Lage sein:
Sammeln Sie alle Informationen, die für die Erstellung eines Sensorplans für Belegungs- und Personenzählsensoren erforderlich sind.
Identifizieren Sie Hindernisse für die Installation von Hardware
Erstellen Sie einen Sensorplan, der allen Beteiligten den Installationsort der Hardware anzeigt.
Ein Sensorplan ist ein Dokument, das allen Beteiligten (Gebäudemanager, IT, Installationspartner, ...) zeigt, wo Sensoren und andere Hardware installiert werden sollen, unter Berücksichtigung von Sensorerfassungsbereichen, Hindernissen usw.
Im Rahmen eines Workplace Analytics-Projekts wird der Sensorplan konkrete Beispiele liefern und Diskussionsthemen vorschlagen.
Mittel der Kommunikation zwischen allen Beteiligten
Ein Sensorplan kann als Mittel zur Kommunikation zwischen allen Beteiligten über
Arten von Sensoren und zu installierender Hardware (Facility Manager oder Techniker vor Ort waren möglicherweise nicht Teil des Beschaffungsprozesses, so dass Sie je nach Art des Sensors (z. B. Kopfzahl) eine Verkabelung/ein Loch in der Decke vorsehen müssen; Displays benötigen eine Verkabelung usw.)
Anzahl der zu installierenden Sensoren und anderer Hardware
Installationsort von Sensoren und Hardware (z. B. wo das Loch in der Decke im Vergleich zum Erfassungsbereich sein muss)
Raumnummern/Namen für jeden Besprechungsraum/Wohnzimmer/Arbeitsplatz/Komfortbereich, der von den Sensoren erfasst werden soll
Info |
---|
Tipp: Erstellen Sie ein PowerPoint-Dokument im Format A3, damit es von den Installateuren problemlos in einem großen Format ausgedruckt werden kann. |
Während sich diese Seite hauptsächlich auf die Installation von Präsenz- und Personenzählsensoren konzentriert, finden Sie unter https://spacewell.atlassian.net/wiki/pages/resumedraft.action?draftId=731250689&draftShareId=0560cf13-dc5c-4813-ba1a-399dc43126fb for more information on how to create a similar plan for comfort sensors.
Requirements for Occupancy & Headcount Sensor Plan
Following information is required to set up a good sensor plan:
Ceiling heights
für weitere Informationen darüber, wie man einen ähnlichen Plan für Komfortsensoren erstellt.
Anforderungen für Belegungs- und Personenzahlsensorplan
Die folgenden Informationen sind erforderlich, um einen guten Sensorplan zu erstellen:
Deckenhöhen
Aktueller Grundriss mit aktuellen Möbelzeichnungen
Superposition Reflected Ceiling Plan (RCP) file, which will provide information on ceiling height, type of ceiling and ideally also information on where light fixtures are installed, where to find HVAC, AC ducts etc (superposition = to reflect all elements on the ceiling that may occlude or interfere with the sensor detection area)Table design information sheets (material, length, depth, where are cable trays positioned-Datei, die Informationen über die Deckenhöhe, die Art der Decke und idealerweise auch Informationen darüber enthält, wo Beleuchtungskörper installiert sind, wo sich HLK- und Klimakanäle befinden usw. (Superposition = Reflexion aller Elemente an der Decke, die den Erfassungsbereich des Sensors verdecken oder stören könnten)
Infoblätter für die Tischkonstruktion (Material, Länge, Tiefe, Position der Kabelkanäle, ...)
Knowing heights of table partitioning: the higher, the more they will interrupt the detection area
Materials of the walls (glass, fabric) , important for
rooms smaller than 4x4m and for displays (where can they be attached?)
pointgrab could see trough glass, so keep count area 0.5m away from glass
if possible: videos or pictures that show the materials of the walls (glass, fabric), information on ceiling fabric, big obstructions like chandeliers or other
Parts of a good sensor plan
Possible version control (version, date, contributor, changes made)
Project context (any possible on-site information that is relevant to any of the stakeholders; for example a hospital context, trading floors with limited access etc)
Workplace Hardware Scope: Number of sensors, hardware touch points
Comments
Sensor placement
(Needs to be based on latest floor plans! Ideally including latest furniture drawings)
Numbers of different sensors for each floor
For headcount and motion sensors for meeting rooms: based on the ceiling / installation heights, you can define the detection area (remember that the Device is always in the middle of the Detection Area, which is measured at ground level); see below chapter on Best Practices of Determining the Detection Area + following pages for more information:
Pointgrab Height ~ Detection Area: detection area is a rectangle
VergeSense Height ~ Detection Area: detection area is a rectangle
Xovis Height ~ Detection Area: detection area is a rectangle
Motion Tabs Height ~ Detection Area: detection area is an ellipse
For comfort sensors, see Materialien der Wände (Glas, Stoff), wichtig für
Räume, die kleiner als 4x4m sind, und für Bildschirme (wo können sie angebracht werden?)
Pointgrab kann durch Glas hindurchsehen, daher sollte der Zählbereich 0,5 m vom Glas entfernt sein.
wenn möglich: Videos oder Bilder, die die Materialien der Wände zeigen (Glas, Stoff), Informationen über Deckenmaterial, große Hindernisse wie Kronleuchter oder andere
Sensor plans of different floors, incl
Kenntnis der Höhe der Tabellenaufteilung: je höher, desto mehr unterbrechen sie den Erfassungsbereich
Bestandteile eines guten Sensorplans
Mögliche Versionskontrolle (Version, Datum, Mitwirkender, vorgenommene Änderungen)
Projektkontext (alle möglichen Vor-Ort-Informationen, die für die Beteiligten relevant sind, z. B. Krankenhauskontext, Geschäftsräume mit eingeschränktem Zugang usw.)
Workplace Hardware Umfang: Anzahl der Sensoren, Hardware-Touchpoints
Kommentare
Platzierung der Sensoren
You might notice that some sensors don't hang above the count area. That's because there were some obstructions above the count areas, meaning areas that needed to be measured (see examples of possible obstructions below).
As long as the Detection area of the sensor (blue transparent rectangle in images below) covers the count area (yellow rectangle), you're good. As you can see here, we decided to keep the Count Area restricted to the Informal Seats (left example), and not take into account the hallway. Sensors were attached to suspended cable trays in this case.
Sensor plan of our own offices in the Netherlands
Examples of possible obstructions/sensor placement according to guidelines not 100% possible
Below list of examples of possible obstructions (where sensor placement according to guidelines is not 100% possible), is just to give you an idea of what you might run into.
Each kind of sensor comes with a set of installation guidelines that provide the Spacewell subscribed accuracy, but sometimes it's just not possible to follow them to the letter in all locations. Yet all stakeholders must understand that if the installation is not according to the guidelines, measurement accuracy will be impacted (which could lead to more false positives or false negatives).
These examples show how important it is to have an on-site-visit; or a lot of pictures or a walk through while on a call.
desks
cable trays/bars under the table
concentration spaces
covered with fabric
is there a table/something in another material, where the sensor would attach?
ceilings
ceiling too high compared to max ceiling height for resp. sensor (need to think of other installation height, eg suspended cable trays)
chandeliers or other obstructions hanging from the ceiling
projector hanging from the ceiling
HVAC tubes
cable trays
curved ceiling
- ceiling is divided into different parts/not flat
(Muss auf den neuesten Grundrissen basieren! Idealerweise einschließlich aktueller Möbelzeichnungen)
Sensorpläne der verschiedenen Etagen, inkl.
Anzahl der verschiedenen Sensoren für jedes Stockwerk
Für Headcount- und Bewegungssensoren für Besprechungsräume: Basierend auf den Decken-/Installationshöhen können Sie den Erfassungsbereich definieren (denken Sie daran, dass sich das Gerät immer in der Mitte des Erfassungsbereichs befindet, der auf Bodenhöhe gemessen wird); weitere Informationen finden Sie im Kapitel Best Practices zur Bestimmung des Erfassungsbereichs + auf den folgenden Seiten:
Pointgrab Höhe ~ ErfassungsbereichErkennungsbereich ist ein Rechteck
VergeSense Höhe ~ ErfassungsbereichErkennungsbereich ist ein Rechteck
Xovis Höhe ~ ErfassungsbereichErkennungsbereich ist ein Rechteck
Motion Tabs Höhe ~ ErfassungsbereichErfassungsbereich ist eine Ellipse
Für Komfortsensoren, siehe https://spacewell.atlassian.net/wiki/pages/resumedraft.action?draftId=731250689&draftShareId=0560cf13-dc5c-4813-ba1a-399dc43126fb : zone covered per sensor (realize that a sensor only tracks the comfort in the spot of installation, so be mindful of not making the "covered zone" not too large. Best practice is not to group workplaces of which some are facing the sun in the morning with workplaces that get the afternoon sun)
Headcount installation direction: Sensors are displayed as circular icons on the floor plan, with an arrow pointing in their view direction (general convention is either pointing upward or to the right of the sensor plan).
Ideally, there are 3 parts to the Sensor Plan:
Sensor Detection Zone layout (shows the detection zones of each sensor, including stitching/detection area overlap): to be used to discuss which areas will be tracked
Sensor Installation layout (with measurements on 2 walls): to be used as installation instruction
(in case of headcount sensors) Area plan with all count areas (areas that need to be tracked): to be used as briefing for the consultant setting up the configuration (eg max 10 areas per Pointgrab; max 8 per Vergesense device)
Assuming that the planner is the one that crops the image and provides the plan for upload in the headcount management tool: When extracting in CAD floor plan, it's possible to provide X,Y coordinates for sensor install in the headcount management tool
Determining Detection Area: Best Practices
Mind that the detection area is measured on floor level: any person standing on the edge of the detection area might not get picked up.
→ Avoid setting up count area at the edge of the detection area. It's a best practice to include 1.5.m coverage on all sides
For meeting rooms: Because of the above mentioned edge of the detection area & because you never know how a room might be used in future, it's best practice that the detection area should cover the whole room, even if that means adding an additional sensor to the room
Specific for headcount sensors:
If more than 1 sensor is used to cover an area, these will need to be "stitched" together in the software. For Pointgrab: Allow an overlap of 0.5m in the detection area of 2 sensors that lie side-by-side and need to be stitched.
Traffic line: 1 single sensor for 1 traffic line (this takes into account for CPU and calculations, otherwise accuracy will drop)
Tracking Workplaces through headcount sensors?
With Pointgrab: 1 single sensor can cover up to 10 count areas
With VergeSense: 1 single sensor can cover up to 8 count areas
Pointgrab can see trough glass, so keep count area 0.5m away from glass
title | How do I define count areas? |
---|
A count area is where you want to track people.
Standard rule:
1 meeting room = 1 count area. Depending on the size of the meeting room and the installation height, more than 1 sensor might be needed to cover the count area (allow for overlap).
For Pointgrab, remember that a PointGrab Count Area is rectangular in shape and needs to be covered entirely by Sensor Detection Areas (Count Area smaller than sum of Detection Areas).
1 workplace = 1 count area
a workplace count area is minimum 1m x 1m
a workplace count area should cover both
about 50cm of the front of the table (where we might track the employee that is leaning over the desk/hunched over the computer
at least 50 cm behind the seat (ideally more, because employees might be leaning backward or side wards talking to colleagues)
There can be exceptions, for example Training Rooms: is it more important to track the utilization of the room, or more important to track the occupancy of individual seats?
Following training room has 22 seats drawn in. If it's enough to track the room: the detection area of 2 sensors combined is enough to cover the dimensions of the room. Yet if you want to measure which seat is more popular of all 22 seats, you will need 3 sensors.
In this next example the object on the left might be just a high standing table for discussions, rather than 4 individual work spaces (as drawn in on the right).
title | How do I make sure not to exceed max count areas per sensor? |
---|
Even if the Detection Area of a sensor might cover more than 8 (for VergeSense) or 10 (for Pointgrab) Count Areas, the platforms will not allow you to configure more. So you'll have to foresee more sensors in order to cover all count areas.
Example of Detection Areas for 4 headcount sensors
Example of the split in count areas (1 sensor = max 10 count areas for a Pointgrab device) for the two bottom sensors
Examples of sensor plans
This example shows "Sensor Detection Zone layout" (not yet highlighting the individual Workplace Areas that would be covered), differentiating between open spaces (pink) and closed spaces (green). This is not a must.
What is expected though, is to clearly show Headcount installation direction.
In the following example, the ceiling was very high and we needed to get creative.
Erfasste Zone pro Sensor (beachten Sie, dass ein Sensor nur die Behaglichkeit am Installationsort erfasst, achten Sie also darauf, die "erfasste Zone" nicht zu groß zu machen. Es empfiehlt sich, Workplaces, von denen einige morgens der Sonne zugewandt sind, nicht mit Workplaces zu gruppieren, die in der Nachmittagssonne liegen.)
Installationsrichtung der Kopfzählung: Die Sensoren werden als kreisförmige Symbole auf dem Grundriss angezeigt, wobei ein Pfeil in ihre Blickrichtung zeigt (die allgemeine Konvention ist, dass sie entweder nach oben oder nach rechts auf den Sensorplan zeigen).
Im Idealfall besteht der Sensorplan aus 3 Teilen:
Anordnung der Sensor-Erkennungsbereiche (zeigt die Erkennungsbereiche jedes Sensors, einschließlich der Überlappung der Erkennungsbereiche): wird verwendet, um zu besprechen, welche Bereiche verfolgt werden sollen
Sensor Installationslayout (mit Messungen an 2 Wänden): als Montageanleitung zu verwenden
(im Falle von Kopfzahlsensoren) Gebietsplan mit allen Zählgebieten (Bereiche, die verfolgt werden müssen): als Einweisung für den Berater, der die Konfiguration einrichtet (z. B. maximal 10 Bereiche pro Pointgrab; maximal 8 pro Vergesense-Gerät)
Angenommen, der Planer ist derjenige, der das Bild zuschneidet und den Plan zum Hochladen in das Headcount-Management-Tool bereitstellt: Beim Extrahieren eines CAD-Grundrisses ist es möglich, X,Y-Koordinaten für die Installation der Sensoren im Headcount-Management-Tool bereitzustellen.
Bestimmung des Erfassungsbereichs: Bewährte Praktiken
Beachten Sie, dass der Erfassungsbereich auf Bodenhöhe gemessen wird: Personen, die am Rand des Erfassungsbereichs stehen, werden möglicherweise nicht erfasst.
→ Vermeiden Sie es, den Zählbereich am Rande des Erfassungsbereichs einzurichten. Am besten ist es, auf allen Seiten einen Bereich von 1,5 m abzudecken.
Für Besprechungsräume: Wegen des oben erwähnten Randes des Erfassungsbereichs und weil man nie weiß, wie ein Raum in Zukunft genutzt werden könnte, sollte der Erfassungsbereich am besten den gesamten Raum abdecken, auch wenn das bedeutet, dass ein zusätzlicher Sensor im Raum angebracht werden muss.
Speziell für Kopfzahlsensoren:
Wenn mehr als 1 Sensor zur Erfassung eines Bereichs verwendet wird, müssen diese in der Software zusammengefügt" werden. Für Pointgrab: Lassen Sie eine Überlappung von 0,5 m im Erfassungsbereich von 2 Sensoren zu, die nebeneinander liegen und zusammengefügt werden müssen.
Verkehrslinie: 1 einzelner Sensor für 1 Verkehrslinie (dies berücksichtigt CPU und Berechnungen, ansonsten sinkt die Genauigkeit)
Verfolgung von Workplaces durch Sensoren für die Mitarbeiterzahl?
Mit Pointgrab: 1 einzelner Sensor kann bis zu 10 Zählbereiche abdecken
Mit VergeSense: 1 einzelner Sensor kann bis zu 8 Zählbereiche abdecken
Pointgrab kann durch Glas hindurchsehen, daher sollte der Zählbereich 0,5 m von Glas entfernt sein.
Expand | ||
---|---|---|
| ||
Ein Zählbereich ist der Bereich, in dem Sie Personen verfolgen wollen. Standardregel:
Es kann Ausnahmen geben, z. B. Schulungsräume: Ist es wichtiger, die Auslastung des Raums zu erfassen, oder wichtiger, die Belegung einzelner Plätze zu erfassen? Der folgende Schulungsraum hat 22 eingezeichnete Sitzplätze. Wenn es ausreicht, den Raum zu erfassen: Der Erfassungsbereich von 2 Sensoren zusammen reicht aus, um die Abmessungen des Raums abzudecken. Wenn Sie jedoch messen wollen, welcher Sitzplatz von allen 22 Plätzen am beliebtesten ist, benötigen Sie 3 Sensoren. In diesem nächsten Beispiel könnte es sich bei dem Objekt auf der linken Seite um einen Stehtisch für Besprechungen handeln und nicht um 4 Einzelarbeitsplätze (wie auf der rechten Seite eingezeichnet). |
Expand | ||||
---|---|---|---|---|
| ||||
Auch wenn der Erfassungsbereich eines Sensors mehr als 8 (für VergeSense) oder 10 (für Pointgrab) Zählbereiche abdecken kann, erlauben die Plattformen nicht, dass Sie mehr konfigurieren. Sie müssen also mehr Sensoren vorsehen, um alle Zählbereiche abdecken zu können.
|
Beispiele für Sensorpläne
Dieses Beispiel zeigt das "Sensor Detection Zone Layout" (noch nicht die einzelnen Workplace-Bereiche, die abgedeckt werden sollen), wobei zwischen offenen Bereichen (rosa) und geschlossenen Bereichen (grün) unterschieden wird. Dies ist kein Muss.
Es wird jedoch erwartet, dass die Richtung der Headcount-Installation klar erkennbar ist.
Im folgenden Beispiel war die Decke sehr hoch und wir mussten kreativ werden.
Sie werden feststellen, dass einige Sensoren nicht über dem Zählbereich hängen. Das liegt daran, dass sich über den Zählbereichen Hindernisse befinden, d. h. Bereiche, die gemessen werden müssen (siehe Beispiele für mögliche Hindernisse unten).
Solange der Erfassungsbereich des Sensors (blaues transparentes Rechteck in den Bildern unten) den Zählbereich (gelbes Rechteck) abdeckt, ist alles in Ordnung. Wie Sie hier sehen können, haben wir uns entschieden, den Zählbereich auf die informellen Sitzplätze (Beispiel links) zu beschränken und den Flur nicht zu berücksichtigen. Die Sensoren wurden in diesem Fall an aufgehängten Kabelkanälen befestigt.
Sensorplan unserer eigenen Büros in den Niederlanden
Beispiele für mögliche Behinderungen/Sensorplatzierung nach Richtlinien nicht 100% möglich
Die folgende Liste mit Beispielen für mögliche Hindernisse (bei denen die Platzierung der Sensoren gemäß den Richtlinien nicht zu 100 % möglich ist) soll Ihnen nur eine Vorstellung davon vermitteln, worauf Sie stoßen könnten.
Für jede Art von Sensor gibt es eine Reihe von Installationsrichtlinien, die die von Spacewell angegebene Genauigkeit gewährleisten, aber manchmal ist es einfach nicht möglich, diese Richtlinien an allen Standorten genau zu befolgen. Dennoch müssen alle Beteiligten verstehen, dass die Messgenauigkeit beeinträchtigt wird, wenn die Installation nicht den Richtlinien entspricht (was zu mehr falsch-positiven oder falsch-negativen Ergebnissen führen kann).
Diese Beispiele zeigen, wie wichtig ein Vor-Ort-Besuch ist; oder eine Menge Bilder oder ein Rundgang während eines Anrufs.
Schreibtische
Kabelkanäle/-stangen unter dem Tisch
Konzentrationsräume
mit Stoff bespannt
Gibt es einen Tisch oder etwas in einem anderen Material, an dem der Sensor befestigt werden kann?
Decken
Decke zu hoch im Vergleich zur max. Deckenhöhe für den jeweiligen Sensor (andere Einbauhöhe berücksichtigen, z.B. abgehängte Kabeltrassen)
Kronleuchter oder andere von der Decke hängende Hindernisse
von der Decke hängender Projektor
HVAC-Rohre
Kabelrinnen
geschwungene Decke
Decke ist in verschiedene Teile unterteilt/nicht flach
Expand | ||||
---|---|---|---|---|
|
| |||
Von der Decke herabhängende Beleuchtungskörper, Lüftungskanäle, Kabelkanäle oder andere Gegenstände können die Sicht auf die Sensoren behindern. Auch hohe Möbel wie Schränke können die Sicht behindern.
For the pictures above, where we needed to cover the yellow boxed areas highlighted in the plans below, we installed the sensors on cable trays hanging above the hallway. The detection area of the sensor (blue rectangle) covers the yellow box (which will then be configured as the count area). |
Edge cases
title | Informal areas without tables |
---|
In these cases, motion tabs can only be used to monitor general presence (not individual people), see Motion sensor installation in Meeting Rooms
If you want to know how many people (utilization) are in these areas, you need to use headcount sensors
Für die Bilder oben, wo wir die in den Plänen unten hervorgehobenen gelben Kästen abdecken mussten, haben wir die Sensoren auf über dem Flur hängenden Kabelträgern installiert. Der Erfassungsbereich des Sensors (blaues Rechteck) deckt den gelben Kasten ab (der dann als Zählbereich konfiguriert wird). |
Grenzfälle
Expand | ||
---|---|---|
| ||
In diesen Fällen können die Bewegungsmelder nur zur Überwachung der allgemeinen Anwesenheit (nicht einzelner Personen) verwendet werden, siehe Motion sensor installation in Meeting Rooms Wenn Sie wissen wollen, wie viele Personen sich in diesen Bereichen aufhalten (Auslastung), müssen Sie Personenzählsensoren verwenden. |
Expand | ||||
---|---|---|---|---|
|
| |||
In diesen Fällen können die Bewegungsmelder nur zur Überwachung der allgemeinen Anwesenheit (nicht einzelner Personen) verwendet werden. Die Tische und Stühle sind zu "beweglich", können umgestellt werden usw. Außerdem sind die Tische nicht tief genug, so dass es nicht möglich ist, mithilfe von Bewegungssensoren genaue Angaben zur Belegung zu machen. Wenn Sie wissen wollen, wie viele Personen sich in diesen Bereichen aufhalten (Auslastung), müssen Sie Personenzählsensoren verwenden. |
Expand | ||||
---|---|---|---|---|
| Because these cubicles are open, there is a high risk of false positives. It’s possible to install a motion sensor per workplace (see
| |||
Da diese Kabinen offen sind, besteht ein hohes Risiko von Fehlalarmen. Es ist möglich, einen Bewegungsmelder pro Workplace zu installieren (siehe Motion sensor installation at Workplaces), but make sure the quality assurance is followed and data is monitoredaber stellen Sie sicher, dass die Qualitätssicherung eingehalten wird und die Daten überwacht werden. |
Expand | ||||
---|---|---|---|---|
|
| |||
Im folgenden Beispiel eines Besprechungsraums ist es nicht möglich, die Anwesenheit einzelner Personen zu erfassen. Je nachdem, was erforderlich ist,
|
Expand | ||
---|---|---|
| ||
Depending on the installation height, it’s possible that the detection area is smaller than the meeting room dimensions. If the detection area is smaller than the anticipated count area,
In the above example:
|
Exercise
| |
Je nach Installationshöhe ist der Erfassungsbereich möglicherweise kleiner als die Abmessungen des Besprechungsraums. Wenn der Erfassungsbereich kleiner ist als der erwartete Zählbereich,
Im obigen Beispiel:
|
Übung
Können Sie auf dem Beispielsensorplan der zweiten Etage (mit Personenzählsensoren, Bewegungssensoren, Komfortsensoren und Türschaltersensoren) einen Aufmerksamkeitspunkt identifizieren?
Expand | ||
---|---|---|
| ||
Even if the count areas would not go over the edges of the detection ares: In more than 1 case, the headcount sensor would cover more than 10 workplaces (highlighted in red in the image). VergeSense platform only allows to track 8 Count Areas per sensor, Pointgrab allows for 10 Count Areas per sensor. |
| |
Auch wenn die Zählbereiche nicht über die Ränder der Erfassungsbereiche hinausgehen würden: In mehr als einem Fall würde der Headcount-Sensor mehr als 10 Workplaces abdecken (in der Abbildung rot hervorgehoben). Die VergeSense-Plattform erlaubt nur die Verfolgung von 8 Zählbereichen pro Sensor, Pointgrab erlaubt 10 Zählbereiche pro Sensor. |