Difficulty: novice
Content
Table of Contents | ||||
---|---|---|---|---|
|
Learning Objectives
After reading this article, you’ll be able to:
install Bosch Parking Lot Sensor PLS
configure Bosch Parking Lot Sensor PLSIdentify at which steps Quality Assurance can be done
Perform Quality Assurance at each step
Quality Assurance is done throughout the installation project, since there are different steps in the project:
During Motion sensor installation, by the installer
During the Tabs configuration guide process
After Tabs configuration guide, on site
After Space monitor Dashboard setup
Final Validation at project end
Quality Assurance during installation
See Motion sensor installationguide
Quality Assurance during configuration
See Tabs configuration guideguide
Quality Assurance after configuration
Below verifications should be written down, signed and added to the project documentation.
Review installation location
.
Following excel contains the different steps. Make sure to download, sign and save with the project information.
View file | ||
---|---|---|
|
Quality Assurance before installation (only for LoRa sensors)
Note |
---|
Motion sensors connect over the LoRa network. Make sure you install your LoRa hub before installing the sensors (check out LoRa Gateways / Hubs installation guides for more information). |
1. Spacewell Implementation Consultant to check gateway status on sensor platform
2. If possible: Spacewell Implementation Consultant to add sensor upfront to Studio and check after gateway installation if data comes through in Studio
Quality Assurance during installation
Info |
---|
If the situation you are facing deviates from these instructions/prerequisites, please contact Spacewell. Pictures / Drawings say more than a 1000 words. |
Use the Placement Guides that are made available by Spacewell, see Install & Configure Gateways & Sensors .
Place the sensor sticker to the sensor plan or fill in the prepared excel (see Prepare batch import file before installation)
When installing sensors that have been installed elsewhere in the past (procedure to be defined with Spacewell Implementation Consultant): indicate the sensor ID on the sensor plan. Remember that every Tabs device ID is in hex (The values of a hexadecimal digit can be: 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F)
Installer to take snapshots / examples of sensor placement during installation
Scan the sensor plan with the stickers of the sensor IDs
Send the snapshots and sensor plan to your Spacewell Implementation Consultant, who will use it to import the sensors in the Workplace Platform and will keep the files in the internal project folder
Visual inspection
Check that sensors are placed according to sensor placement guides; not hindered by cables, pipes, light fixtures or other obstructionsVerification they are installed in their planned locations, with the correct view direction
Blue light when waving hand in front of sensor
Quality Assurance during configuration/sensor deployment in Workplace Platform
Remember most (LoRa) device IDs are in hex (The values of a hexadecimal digit can be 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F)
If device ID not readable in sensor plan: check sensor platform
Does the device ID exist?
Is it connecting to the correct hub?
If mapping done based on excel (see Prepare batch import file before installation)
Export sensor devices excel from Studio
Export MCS location IDs excel from MCS
Use VLOOKUP to map to sensor device ID to MCS location
Once VLOOKUP is executed check manually if done right
Check begin, mid and end of excel
Check https://spacewell.atlassian.net/wiki/spaces/KB/pages/492407/Sensor+Health
Check for white spaces on live floorplan (red on Studio health view). These location could be missing mapping.
Quality Assurance after configuration/on-site
The Quality Check after configuration/on-site can happen after the mapping of the sensors in Workplace back-end Studio is done.
To be done by someone who didn’t install the sensors
Make sure you have access to the live floorplan via http://go.cobundu.com
Can be accessed via mobile phone as well
Make sure to bring the sensor plan
Ideally you have access to https://studio.cobundu.com , so that you can immediately make some changes
Below verifications should be written down, signed and added to the project documentation.
Expand | ||
---|---|---|
| ||
|
Quality Assurance for Workplace installation
Expand | ||
---|---|---|
| ||
1 Sensor with cap per desk should be installed differently depending on desk mode:
| ||
|
Expand | ||
---|---|---|
| ||
The The comprehensive test must be performed for at least 1 meeting room and 1 common workplace area (if set up)
|
Quality Assurance for Workplace installation (Tabs motion)
Expand | ||||
---|---|---|---|---|
| ||||
1 Sensor with cap per desk should be installed differently depending on desk mode:
|
Expand | ||
---|---|---|
| ||
|
Expand | ||
---|---|---|
| ||
|
Expand | ||
---|---|---|
| ||
Sit down at a desk, wiggle your legs and turn the chair. Make sure the sensors of neighbouring desks do not trigger false positives; the floorplan must not color red |
Expand | ||
---|---|---|
| ||
|
Quality Assurance for Meeting Room installation (Tabs motion)
Expand | ||
---|---|---|
| ||
Sensor(s) without cap should be installed on the ceiling, in the middle of the room: perpendicular to room (long side sensor parallel to short side room) |
Expand | ||
---|---|---|
| ||
|
Quality Assurance for installation in Rooms under 4x4m (Tabs motion)
Expand | ||
---|---|---|
| ||
Sensor without cap should be installed on the wall next to the door (at the entrance of the room), facing inward. If the door opens to the inside, there might be a reflection on that door. It might be advisable to then place the sensor behind the door (assuming people close the door to start using this space – and thereby trigger the sensor). |
Expand | ||
---|---|---|
| ||
|
Quality Assurance for Pointgrab
Expand | ||
---|---|---|
| ||
Walk along the edge of the Count Area and verify when the sensor detects occupancy. Compare the Count area of the installed device with the configured area(s). Especially when workplaces are tracked by a Pointgrab device, it should be easy to verify that the correct workplace area lights up when the relevant location is occupied. |
Quality Assurance for headcount setup
Expand | ||
---|---|---|
| ||
Verify the count areas are set up correctly, not too large. When walking in a count area of the sensor, occupancy must be triggered:
When walking next to a count area of the sensor: Make sure the sensors do not trigger false positives; the location must not color red on the floorplan. |
Expand | ||
---|---|---|
| ||
|
Expand | ||
---|---|---|
| ||
|
Expand | ||
---|---|---|
| ||
|
Quality Assurance for traffic / footfall count
Expand | ||
---|---|---|
| ||
Verify the traffic line and count areas are set up correctly, not too small. When walking in a count area of the sensor, traffic count must be triggered:
When walking further away from a count area of the sensor: Make sure the sensors do not trigger false positives. |
Quality Assurance after Dashboard setup
Final Validation at project end
Acceptance document stating deliverables (hardware, dashboards), date, name
Description of the project
Floorplans: changes, rendering, upload
Sensors and hubs: delivery, assistance in installation, upload, mapping
Setup live floorplan and kiosks, available through https://go.cobundu.com/
Creation of dashboard XYZ, available through https://go.cobundu.com
The volume and quality of the above-mentioned goods and/or services are in accordance with the agreements and scope agreed upon. Consequently, the elements stated above are fully accepted.